Air source heat pumps
WPL 13 E – Technical Data
-
Technical data
Energy efficiency class, heat pump W35
A++
Energy efficiency class, heat pump W55
A+
Energy efficiency class, composite system (heat pump + controller) W35
A++
Energy efficiency class, composite system (heat pump + controller) W55
A+
Heating output at A7/W35 (EN 14511)
8.93 kW
Heating output at A2/W35 (EN 14511)
8.09 kW
Heating output at A-7/W35 (EN 14511)
6.77 kW
COP at A7/W35 (EN 14511)
4.35
COP at A2/W35 (EN 14511)
3.76
COP at A-7/W35 (EN 14511)
3.20
SCOP (EN 14825)
3.85
Sound power level (EN 12102)
64 dB(A)
Sound power level, outdoor installation (EN 12102)
64 dB(A)
Min./max. application limits for heat source
-20...40 °C
Max. application limit on the heating side
60 °C
Height
1116 mm
Width
784 mm
Depth
1182 mm
Weight
205 kg
Rated voltage, compressor
400 V
Rated voltage, emergency/auxiliary heater
400 V
Rated voltage, control unit
230 V
Refrigerant
R407C
Colour
white
The housing required for indoor or outdoor installation is available as an accessory.
Wall outlets and air hoses for indoor installation must be ordered separately and are available as accessories in various versions.
Installation Information:
Please ask your local power supply utility or a registered electrician to install appliances that are not fully wired, i.e. ready to plug in. The electrician should also be able to assist you with obtaining the agreement of the respective power supply utility required for the appliance installation.